How to eliminate: "Cannot apply any pipe spacing": Difference between revisions
Jump to navigation
Jump to search
(Created page with "<IS_AUTOPAGE/> <IS_HELP id="HS26"/> {{Article table |commercial_product1=InstalSystem 5 |p2 =<!--gdy jest kolejny produkt handlowy, zamienić na->"produkt_han...") |
X - AR-THERM (talk | contribs) No edit summary |
||
| Line 19: | Line 19: | ||
}} | }} | ||
== | ==Description== | ||
The message is displayed when the program cannot select pipe spacing among available options: | |||
* '''<IS_TS id=strErrPowGrzejnaAllVarInvalid/>''' | * '''<IS_TS id=strErrPowGrzejnaAllVarInvalid/>''' | ||
Lack of possibility to choose pipe spacing is usually caused by: | |||
* | * too high radiant system supply temperature, | ||
* | * limited number of available pipe spacing options. | ||
== | ==Solution== | ||
# | # Too high radiant system supply temperature. | ||
#* | #* Insertion of covering to ''<IS_TS id=strSPGCh/>''.<br/>{{#ev:youtube|lKMdz7HFhGA|900||||rel=0}}<br clear="all"/> | ||
#* | #* Corection (lowering) of radiant system supply temperature.<br/>{{#ev:youtube|aemexyXYZcY|900||||rel=0}} | ||
#* | #* Correction (rise) ''<IS_TS id=stringTppMaxSW/>'' - maximum heating/cooling surface temperature.<br/>{{#ev:youtube|GpPut7giyjA|900||||rel=0}} | ||
# | # Too limited number of available pipe spacing options. | ||
#* | #* Turning on of additional pipe spacing options on the ''<IS_TS id=strDostepneOdstepyUkladania/>'' list.<br/>[[File:TP-Cannot-apply-any-pipe-spacing-VA.png|900 px|thumb|left|1. ''<IS_TS id=strDostepneOdstepyUkladania/>'']]<br clear="all"/> | ||
[[Category:InstalSystem 5]] | [[Category:InstalSystem 5]] | ||
[[Category:TYPOWY PROBLEM]] | [[Category:TYPOWY PROBLEM]] | ||
Revision as of 09:20, 28 August 2019
| Product | InstalSystem 5 |
| Type of article | TYPOWY PROBLEM |
| Source for translation | WYDANIE Rev. 15.3 |
Description
The message is displayed when the program cannot select pipe spacing among available options:
- CANNOT APPLY ANY PIPE SPACING
Lack of possibility to choose pipe spacing is usually caused by:
- too high radiant system supply temperature,
- limited number of available pipe spacing options.
Solution
- Too high radiant system supply temperature.
- Insertion of covering to Heating/Cooling Zone.
- Corection (lowering) of radiant system supply temperature.
- Correction (rise) θsurf max - maximum heating/cooling surface temperature.
- Insertion of covering to Heating/Cooling Zone.
- Too limited number of available pipe spacing options.